Rated voltage, V | 240 |
Rated voltage frequency, Hz | 47 – 65 |
Harmonical configuration (non-sinusoidality) of power supply voltage | EN 61000-3-2 (IEC 1000-3-2) |
Adjustable settings ranges: – Minimal voltage tripping threshold (Umin), V – Maximal voltage tripping threshold (Umax), V – Auto-reclosing time delay, sec | 180 – 240 250 – 300 5 –900 |
Device level protection | IP30 |
Fixed tripping time delay when input voltage exceeds the minimal tripping threshold (Umin), sec | 7 |
Fixed tripping time delay when input voltage exceeds the maximal tripping threshold (Umax), sec | 1 |
Fixed tripping time delay in case of voltage decrease more than 60V than the adjusted minimal voltage tripping threshold (Umin), sec | 0.12 |
Fixed tripping time delay in case of voltage increase more than 30V than the adjusted maximal voltage tripping threshold (Umax), sec | 0.12 |
Maximal commutation current (active power load), A (not less than) AC-1 type | 32 |
Accuracy for tripping basing the voltage level measurement, V | < 3 |
Minimal operation voltage level at which PH-102 will keep working, V Maximal operation voltage level at which PH-102 will keep working, V | 120 400 |
Voltage hysteresis, V | 4 |
Protection class against electric shock | II |
Overvoltage category | II |
Permissible contamination level | II |
Nominal voltage of isolation, V | 450 |
Rated impulse withstand voltage, kV | 2.5 |
Guide section of connecting plugs, mm2 | 0.3-3.3 |
Maximum moment of an inhaling of screws of connection terminal, N*m | 1.2 |
Operational temperature range, °С | from -30 to + 55 |
Total power consumption, mA | < 15 |
Commutation lifetime of the output contacts: – under 32A power load, times (not less than) – under 5A power load, times (not less than) | 100 000 1 000 000 |
Outer dimensions, mm | 80 х 120 х 43 |
Net weight, kg | 0.250 |
Wall mounting in vertical position in order to read the digits of the front panel indicator |