Rated phase/line voltage, V | 240/415 |
Mains frequency, Hz | 45-55 |
Harmonical configuration (nonsinusoidality) of power supply voltage | EN 61000-3-2 (IEC 1000-3-2) |
Adjustable range for Umin, % of nominal value | 5-25 |
Adjustable range for Umax, % of nominal value | 5-25 |
Adjustable range for phase imbalance/asymmetry, % | 5-20 |
Adjustable range for Tmin, sec | 0-20 |
Adjustable range for Toff, sec | 0-10 |
Adjustable range for Ton, sec | 0-600 |
Minimum trip delay when threshold settings are reached, sec | 0.1 |
Reset/energization delay when the relay energizes, sec, not more than | 0.2 |
Voltage hysteresis, V | 5-6 |
Accuracy of trip threshold for voltage, V, not more than | 3 |
Phase imbalance accuracy, %, not more than | 1.5 |
Safe operating voltage, % of rated value | 30-110 |
Power required (under load), VA, not more than | 3.0 |
Maximum switched current of output contacts, A | 5 |
Output contacts life: - under load 5A, no less than, operations
- under load 1A, no less than, operations
| 100000 1 mln. |
Protection degree of: | IP40 IP20
|
Permissible contamination level | II |
Overvoltage category | III |
Nominal voltage of isolation, V | 450 |
Rated impulse withstand voltage, kV | 4 |
Cross-section area of connection terminals, mm² | 0.5-2 |
Maximum torque of terminal fixing, N*m | 0.4 |
Operating temperature range, °C | from -35 to +55 |
Weight, no more than, kg | 0.200 |
Case dimensions 4 modules of S-type |
Mounting 35 mm DIN-rail |
Mounting position as desired |