DRY TRANSFORMER TEMPERATURE CONTROLLER TR-100

Product Details:

Voltage24 to 265V AC-DC
Temperature Rangeminus 60 to plus 300 deg C
Controller TypeSafety Limit Controller, On/Off Control
Input SensorRTD
BrandNOVATEK ELECTRO
Power24 VDC, 100 to 240 VAC 50/60 Hz
Model NumberTR-100
MaterialFlame retardant plastic
TypeDigital with RS485 Modbus RTU/ASCII communication
MountingFlush Mounting (96 x 96)
Size96 x 96 x 78 mm
Display TypeDigital LED
ApplicationProtection of Dry type Transformers and HV Motors

ТR-100М is microprocessor based device intended to measure and control temperature mode of dry-type transformer with four transducers connected by two or three wire circuit, with subsequently displaying the temperature on the display and sending alarms when any parameters are outside preset limits.

The product can also be used for protection of HV motors and generators.

The product has universal power supply of 24 to 265 V (AC or DC) and connection to network EIA/TIA-485 with MODBUS RTU / ASCII protocol.

The product can be applied with the following types of temperature transducers:

– PT100 – platinum transducer with rated resistance of 100 Ohm, at 0°С;

– PT1000 – platinum transducer with rated resistance of 1000 Ohm, at 0°С;

– PTС1000 (EKS111) – transducer with rated resistance of 990 Ohm, at 25°С;

– PTC (minika) – cold resistance of transducer of 20-250 Ohm.

The structure of ТR-100М is made in plastic housing designed for mounting on the front panel of the board (cabinet) or of the device; dimensions of the housing is 96 x 96 x 110 mm. The housing is made of shockproof, self-extinguishing material.

The product has four channels for temperature measurement, and four output load relays. Each load relay is designated for a particular control parameter (like On/Off cooling systems, Alarm, Tripping, Sensor fault).

The temperature transducers (sensors) of the first three channels measure the temperature of each transformer winding; and the fourth one measures temperature of the transformer yoke or ambient temperature.

In case of dangerous temperature rise of the transformer, the product first will enable alarm system and the cooling fans. If the temperature rise continues and the temperature exceeds the limit value, the product will perform emergency shutdown of the transformer.

In case of temperature sensor fault, TR-100M enables the alarm of the transducer fault.

Additional Information:

  • Item Code: TR-100M
  • Port of Dispatch: New Delhi, India

Basic Specifications:

Description

Value

Operating supply voltage ( ), V

230 / 240

Voltage at which service capability is maintained ( / ), V

24 – 265

Frequency of supply mains, Hz

45 – 65

Consumed power (from mains of ~230 V), W, not more

6.0

Consumed power (from power supply unit +24 V), W, not more

2.2

Quantity of transducers connected, pc.

4

Types of transducers used to measure temperature

РТ100, PT1000,

PTC1000 (EKS111),

PTC (minika)*

Transducers connection circuit

2 / 3-wire

Max. length of transducer wire depending on connection circuit, m

2-wire – to 5 m;

3-wire – to 100 m

Temperature measurement accuracy, °C

± 2

Measured temperature range, °С:

PT100

PT1000

PTC1000 (EKS111)

PTC (minika)

 

minus 60 to +300

minus 60 to +300

minus 50 to +120

+60 to +180

Temperature digital filtering

Available

Quantity of output relays and contacts type, pc.

4 – switching

Commutation life of output contacts of the relay:

  • Electrical lifetime at 10A 250V AC (cos φ = 1.0), time, not less
  • Electrical lifetime at 10А 24V DC, time, not less
  • Mechanical lifetime, time, not less

 

100000

10000

10000000

Specification of output contacts of the relay:

  • Max. switching current at  250 V (cos φ = 1.0), А
  • Max. switching current at  250 V (cos φ = 0.4), А
  • Max. switching current at  30 V, А
  • Max. switching power, VА

10

6

3

2500

Test of output relays

Available

Test of indication

Available

EIA/TIA-485 MODBUS RTU / ASCII

Available

Data storage time, year, not less

15

Product service

Control and distribution device

Rated operating condition

Continuous

Protection rating of front panel

ІР64

Protection rating of housing

IP20

Electric shock protection class

II

Climatic version

NC 3.1

Permissible contamination level

II

Overvoltage category

II

Rated insulation voltage, V

450

Rated impulse withstand voltage, kV

2.5

Wire cross-section for connection to terminals, mm²

0.5 – 2.5

Tightening torque of terminal screws, N*m

0.4

Weight, kg, not more

0.360

Overall dimensions (L x W x H), mm

110 x 98 x 96

Installation is designed on the front panel of the board (cabinet) or device

The product remains functional at any position in space

* – PTC (minika) transducers can be series-connected (by 1, 3, 6 pc.)

 

TR-100M meets the requirements of the following:

  • Low-voltage switchgear; Part 1; General rules (IEC 60947-1:2004, ІDТ);
  • Low-voltage circuit breaker and controller; Part 6-2; multifunctional equipment; Control and safety switching equipment (ІEC 60947-6-2:1992, ІDT);
  • Electromagnetic compatibility; Industrial, scientific and medical RF equipment; electromagnetic interference characteristics; standards and measuring procedure (CISPR 11:2004, IDT);
  • Electromagnetic compatibility; Part 4-2; Testing and measurement techniques; Electrostatic discharge immunity test (IEC 61000-4-2:2001, IDT).